How this is modelled, and what it is not
The room is a lumped pressure network, not a CFD mesh. Around the closed circuit the available
pressure is stack effect plus the server fan head, and the loop flow is
Q = √(Δp / ΣR) with each segment's resistance R = K·ρ/(2A²).
Temperatures come from ΔT = P/(ṁ·cp) and are mixed at each junction, so bypass and
spill-back cool the hot column and weaken the buoyancy that drives the loop. The three equations
are mutually dependent, so they are iterated to a fixed point.
Tracers follow prescribed circuits at the solved local velocity (accelerated on screen by the
time multiplier). The fraction that spills back from the ceiling or bypasses the racks follows the
solved leak shares. What it does not give you: local turbulence, rack-by-rack inlet
temperatures, stratification inside the plenum, or transient behaviour after a change.